A conduit has the following conductors installed:

One (1) phase wire and the neutral of a 4-wire, 3-phase wye-connected system.

Three (3) phase conductors and the neutral of a 4-wire, 3-phase wye-connected system supplying a nonlinear load.

Based upon the total number of current-carrying conductors, the allowable ampacity of each conductor as determined in Table 310.15(C)(1) AND {Table 310-16 } must be adjusted by:
Переглянути це питання
This pull box is to enclose conductors larger than #6 AWG. What is the minimum size pull box that can be used for this installation?

mc010-1.jpg
0%
0%
0%
Переглянути це питання
The minimum length for this pull box enclosing conductors larger than #6 AWG shal be:

mc006-1.jpg

Переглянути це питання
The 4" conduits of this pull box are to enclose the same conductors What is the minimum distance ("C") that shall be maintained between these raceway entries?

mc001-1.jpg
0%
0%
0%
0%
Переглянути це питання
Each yoke or strap containing one or more devices or equipment in a device box counts as ____ conductors.
0%
0%
0%
0%
Переглянути це питання
A square box 4" X 2 1/8" has been installed with cable clamps, two (2) fixture studs and one (1) hickey. What is the maximum number of #12 AWG conductors now allowed to be pulled into this box?
0%
0%
0%
0%
Переглянути це питання
A set of 4/0 feeder conductors enter a panelboard from the bottom and terminate on the single wire lugs of a horizontally mounted circuit breaker. The minimum wire bending space to be maintained between the breaker terminals for these conductors and the cabinet wall would be:
0%
0%
100%
Переглянути це питання
A device box contains the following:

Two (2) 14-3 w/g nonmetallic sheathed cables

Two (2) 3-way swithes (connected to #14 AWG wire)

Two (2) 12-2 w/g nonmetallic sheathed cables

One (1) Duplex receptacle (connected to #12 AWG wire)

Four (4) Cable clamps

What is the minimum cubic volume required for this box?
50%
50%
0%
Переглянути це питання
A 4 X 2 1/8 inch square box has a  3.3 cubic inch plaster ring attached. The conduit serves as the equipment ground and the box contains the following:

Four (4) #12 AWG THHN solid conductors terminating in the box

One (1) Duplex receptacle attached to the above conductors

Two #12 AWG THHN stranded conductors passing through the box

   

How many more #12 AWG conductors are permitted to be added to this box?
0%
0%
0%
0%
Переглянути це питання
A 12 AWG copper conductor requires ____ cubic inch free space within a device box.
0%
0%
0%
0%
Переглянути це питання