2025SU ELC-119-02BL NEC Calculations

Looking for 2025SU ELC-119-02BL NEC Calculations test answers and solutions? Browse our comprehensive collection of verified answers for 2025SU ELC-119-02BL NEC Calculations at moodle.pittcc.edu.

Get instant access to accurate answers and detailed explanations for your course questions. Our community-driven platform helps students succeed!

When the selection of  the overlod device for a motor is not sufficient for starting a motor of the following (10 Hp,  3 phase,  240V,  FLC 23Amps,  temperature rise 30 degrees C),  the overload device shall be permitted to  be increased to 140% of the nameplate FLC of the motor?
100%
0%
View this question
A thermal protector integral with the motor is required to prevent dangerous overheating. Motors greater than 20 amps will be required to be protected by 156% of the FLC given in the Tables 430.248, Table 430.249, and Table 430.250.
0%
0%
View this question
The maximum rating of a inverse time breaker can be increased to what percentage when the minimum size of 115%  is insufficient to starting a motor?

Note : 150 amp Full Load Current for Motor

0%
0%
0%
0%
View this question
The full load amps, from the nameplate of a 50 HP, 480 volt, 3-phase squirrel cage motor is 62 amps. What should be the maximum rating or setting of the instantaneous trip circuit breaker which provides short-circuit and ground-fault protection to this motor circuit? 
0%
0%
0%
0%
View this question
The following motors are connected to a 240 volt, 3-phase, 4-wire feeder. All terminations on this circuit are 75 degree C. (Instantaneous Trip Breakers)

nar001-1.jpg

The overload device for the 7.5 HP motor should be selected to trip at:
0%
0%
0%
0%
View this question
The following motors are connected to a 240 volt, 3-phase, 4-wire feeder. All terminations on this circuit are 75 degree C. (Instantaneous Trip Breakers)

nar001-1.jpg

The minimum size THHN copper conductors for the feeder of this motor circuit would be:
0%
0%
0%
0%
View this question
The following motors are connected to a 240 volt, 3-phase, 4-wire feeder. All terminations on this circuit are 75 degree C. (Instantaneous Trip Breakers)

nar001-1.jpg

If all branch circuit, short-circuit, ground fault protective devices are instantaneous trip breakers, what is the maximum size of the following that can be used for the short-circuit and ground fault protection for the feeder of this circuit?
View this question
The following motors are connected to a 240 volt, 3-phase, 4-wire feeder. All terminations on this circuit are 75 degree C.

nar001-1.jpg

A dual element time delay fuse is to be installed on the 5 HP motor branch circuit. It should have a maximum ampere rating of :
0%
0%
0%
0%
View this question
Where the overload relay of a motor starter will not allow a motor with a marked service factor of 1.15 to start under load, it may be increased to a maximum of:
0%
0%
0%
0%
View this question
The full load current for a 2HP, 230 volt, single-phase motor would be:
View this question